KSO-202Promo

Features

  • Fully prefabricated.
  • Convenient maintenance
  •  Using spring-motor drive you can manually turn it on/off without engaging any additional devices when there is no auxiliary power.
  • Isolated low-voltage (relay) compartment
  • Possible customization to fit non-standard layouts.

 

Design

One-side service chamber is a metal structure made of 2 mm thick steel (bearing structures are 3 mm thick). All components are painted with powder paint.

To ensure the safety of the maintenance staff, the chamber is divided into three isolated compartments: busbar, high-voltage, and low-voltage (relay) compartments.

Support insulators with busbars and busbar breaker are installed in busbar compartment.

HV compartment contains main circuit equipment - vacuum breaker, current transformers, voltage transformers, fuses, line disconnector, and surge arresters.

Installed in the relay compartment are: relay protection and automation microprocessor units, control and metering devices.

The chamber has two doors. Upper door covers the relay compartment. The lower door covers high-voltage equipment.

Busbars are closed by protective housing on the front side.

There are inspection windows in the lower door and protective casing to see the inside of the chamber.

One-side service chambers have internal LED lighting.

Chambers provide for cable end cutting and accomodate the connection of up to four three-phase cables up to 240 mm², as well as six single-phase cables up to 500 mm² with plastic insulation.

Chambers are deparated from each other by metal dividers.

Chambers have several electrical and mechanical interlocks for safe operation.

In two-row arrangement in switchgear space, bus bridges are installed on the chambers.

Bus bridges are of two types - without disconnectors and with disconnectors for busbar sectioning. Switch actuators are placed on the panels 200 mm wide, mounted between the the two end chambers in the row.

SITE NAVIGATION

VIDEO ABOUT TCN-ELECTRO PLANT

IMPLEMENTED PROJECTS

Basic technical parameters

Rated voltage, kV

6; 10

Max. operation voltage, kV

7.2; 12

Rated frequency, Hz

50

Busbar rated current, A

1,000

Main circuit rated current, A

630; 1,000

Control/auxiliary circuit rated voltages, V:

- control AC

- control DC

- voltage transformer circuits

- circuits for lighting inside the chambers

- auxiliary transformer circuits

 

 

220

24; 48; 100

100

12

380

Rated switch breaking current, kA

20

Short-time withstand current, kA

20 (depends on short-time withstand currents of build-in current transformers)

Withstand current time, s:

- chamber with load break switch

- other chambers

- earthing switches

 

1

3

1

Peak withstand current, kA

51

Rated primary current of current transformers, A

30; 50; 75; 100; 150; 200; 300; 400; 600; 800; 1,000

HV fuse fusible link current, А

2…80

Chamber dimensions, mm:

- height

- length

- width

 

2,480

1,100

750; 1,000

Max. weight, kg

600

Insulation as per GOST 516.3-96

Normal, level "b"

Insulation type

Air

Insulation of the main circuit busbars

With uninsulated or partially insulated busbars

Protection class from the front side and butt element

as per GOST 14254-96

IP 31

Service type

One-side service

Withdrawable elements

No withdrawable elements

Type of line HV bays

Cable and bus

One-side service chamber type depending on built-in equipment and bays

With vacuum circuit breaker.

With disconnectors

With power fuses

With current transformers

With voltage transformers

With auxiliary transformer;

Combined

Control type

Local

Climatic modification as per GOST 15150

UZ

Ambient operating temperature, °С

+40 … -45

Max. altitude above sea level, m

1,000

Service life, years

30