KSO-215ESM6

Features

  • Fully prefabricated.
  • Small size.
  • Does not require maintenance
  • Uses switchgear devices that completely exclude open arc inside the cell
  • Front cable connection significantly reduces installation time and cost
  • Possible customization to fit non-standard layouts.

 

Design

KSO-215ЭСМ6 cell is a cabinet of welded steel 2 mm thick. All its elements are painted with powder paint, resistant to mechanical damage.

To ensure high localization ability and operational safety, the cell housing is divided into separate compartments:

– busbar compartment;

– LV compartment (relay protection cabinet);

– HV compartment.

Busbars in the busbar compartment are mounted on the terminals of fixed breaker contacts or load break switches. The compartment is isolated from other cell compartments and from the busbar compartments of other switchboard cells.

In the low-voltage compartment contains microprocessor-based relay protection unit, devices for commercial or technical metering of electrical energy, measuring devices, terminal rows, heating and lighting circuits, automation devices, and operational interlocks. If necessary, the components of  the automated control system can be installed.

Depending on the main circuit layout, HV vacuum circuit-breaker, earthing switch, current transformers, fuses, and voltage transformers can be installed in the HV compartment. Cable bays are also located in the compartments. Vacuum circuit breakers manufactured by AO "PO Eltekhnika" or AO "GK Tavrida Electric" are used as power switch.

The drives of the load break switches, disconnectors, earthing switches, and control devices are located on the front side of the cell. Drives have mechanical position indicators of the main terminals of the switching devices.

On the front side of the door of the relay protection compartment there is a mnemonic scheme that indicates the position of the switching devices by means of the light indication: ON, OFF, or GROUNDED.

The door of the HV compartment has reinforced structure and mechanism, that ensures multi-point fixation to the cell body when the doors are closed.  There are inspecting windows on the cell door.

On the back wall of the cell there are valves to relieve excess pressure and release of combustion products that arise inside the cell in the event of a short circuit.

Interlock devices installed in the chamber and their quantity comply with the requirements of the Electrical Installations Code (EIC), 7th edition, and GOST 12.2.007.4.

LED lights are used for lighting of the cell housing interior.

Basic technical parameters

SITE NAVIGATION

VIDEO ABOUT TCN-ELECTRO PLANT

IMPLEMENTED PROJECTS

Rated voltage, kV

6; 10

Max. rated operating voltage, kV

7.2; 12

Rated frequency, Hz

50

Busbar rated current, A

1,000

Power switch rated current, A

1,000

Load switch breaker rated current, A

630

Disconnector rated current, А

630; 1,000

Auxiliary circuits rated voltage, V

220

Power switch rated breaking current, kA

20

3 s withstand current, kA

20

Withstand current time, s:

- chamber with load break switch

- other chambers

- earthing switches

 

1

3

1

Peak withstand current, kA

51

Normalized parameters of the load break switch tripping current, kA

- max. peak

- initial rms value of periodic component

 

31.5; 40; 51

12.5; 16; 20

Rated primary current of current transformers, A

50; 75; 100; 150; 200; 300; 400; 600; 800; 1,000

Fuse max. rated current, A

200

Fuse rated breaking current, kA

- up to 160 А

- 200 А

 

63

50

Control/auxiliary circuit rated voltage, V:

- control AC

- control DC

- voltage transformer circuits

- circuits for lighting inside the chambers

- auxiliary transformer circuits

 

220

24; 48; 100

100

12

380

Max. closing/breaking time, s:

- power switches

- motor-operated load break switches

- load break switches with closing solenoid

 

0.1 / 0.04

9.0 / 9.0

0.1 / 0.1

Switching durability (number of cycles В - tn - 0), min:

- power switches

- load break switches (at 630 А cutoff current)

 

50

100

Max. dimensions of chambers, (H х W х L), mm:

1,700* х 400 (500) х 880

Insulation as per GOST 516.3-96

Normal, level "b"

Insulation type

Combined (air and solid)

Insulation of the main circuit busbars

With uninsulated busbars

Enclosure protection class as per GOST 14254-96

IP 31

Service type

One-side service

Withdrawable  elements

Without withdrawable elements; with withdrawable elements

Type of line HV bays

Cable

 

 

 

 

 

One-side service chamber type depending on built-in equipment and bays

 

1. with power switch in combination with one or two disconnectors and earthing switch;

2. with load break switch;

3. with load break switch and fuses;

4. with disconnector;

5. with earthing switch;

6. with disconnector and earthing switch;

7. with earthing switch and voltage measuring transformer;

8. with auxiliary transformer;

9. with cable assembly and earthing switch;

Control type

Local and remote

Climatic modification as per GOST 15150

UZ

Ambient operating temperature, °С

+40 … -25

Max. altitude above sea level, m

1,000

Service life, years

30

GEOGRAPHY OF DELIVERIES

CATALOGUE PRINTED VERSION

* Without height of the base and relay compartment

©1999-2018 ООО TCN-electro

 

Sale Department for the Nizhny Novgorod region: +7 (831) 275-888-9

Regional sale department (Russia and CIS countries): +7 (495) 789-49-68

 

7 A, ul. Elektrovoznaya, Nizhny Novgorod, Russia, 603108

office@tcn-nn.ru