KSO-366

Features

• Low price

• Simple and reliable design

• Serviceability

• Chambers are made in several sizes

 

Design

KSO-366 chambers are unitized and irrespective of the arrangement of the main circuit electrical connections have similar design of the main units. Each KSO chamber is a welded metal structure with main circuit equipment inside: load switches, disconnectors, current transformers, and voltage transformers. The handles of the mechanical control actuators for the load break switch (disconnector) and grounding blades are located on the front side of the chamber. At the top of the chamber, along the front side, there is a box with a door where the auxiliary circuit trunks are laid. Access to the camera is provided through the door with a window to inspect the inner zone. Each chamber is lined with a metal sheet on the left end face. LED lights are used for lighting of the cell housing interior.

KSO chambers can be arranged in single-row and double-row layout.

Double-row switchgear requires busbar bridges. There are two types of busbar bridges: without disconnectors or with disconnectors for busbar sectioning. Busbar bridge disconnector drives are mounted on the end panels, which also serve as fencing for the switchgear busbars. The bus bridge with disconnectors is installed only on the end chambers of the switchgear.

There are following mechanical interlocks in KSO chambers:

- interlock against closing of the grounding blades, when the main blades of the load break switch (disconnector) are closed;

- interlock against closing of the grounding blades, when main knives of the main load break switch (disconnector) are closed;

- interlock against closing of the grounding blades, when the main blades of the load break switch (disconnector) are closed;

Grounding of the switchgear busbars can be implemented in a chamber with a voltage transformer or in separate chambers.

Basic technical parameters

Rated voltage, kV

6; 10

Max. rated voltage, kV

7.2; 12

Rated frequency, Hz

50

Busbar rated current, A

630

Main circuit rated current, A

630

Control/auxiliary circuit rated voltages, V:

- control AC

- voltage transformer circuits

- circuits for lighting inside the chambers

- auxiliary transformer circuits

 

 

220

100

12

380

Rated switch breaking current, kA

20

Short-time withstand current, kA

20 (depends on short-time withstand currents of build-in current transformers)

Withstand current time, s

1

Peak withstand current, kA

- chamber with load break switch

- chamber with disconnector

 

51

20

Breaking capacity of the load break switch in normal mode, number of trips

10

Min. mechanical life before overhaul, number of operations

2,000

Rated primary current of current transformers, A

30; 50; 75; 100; 150; 200; 300; 400; 600

HV fuse fusible link current, А

2…100

Dimensions of chambers, (H х W х L), mm:

- dimension 1

- dimension 2

- dimension 3

- dimension 4

 

1,900 х 800 х 800

2,080 х 800 х 800

2,080 х 850 х 1,000

2,080 х 1,000 х 1,000

Max. weight, kg

300

Insulation as per GOST 516.3-96

Normal, level "b"

Insulation type

Air

Insulation of the main circuit busbars

With uninsulated or partially insulated busbars

Enclosure protection class as per GOST 14254-96

front side - IP 31; rest - IP00

Service type

One-side service

Withdrawable  elements

No withdrawable elements

Type of line HV bays

Cable and bus

 

 

 

One-side service chamber type depending on built-in equipment and bays

With load break switch

With disconnector

With load break switch and fuses;

With earthing switch

With current transformers

With voltage transformers

With auxiliary transformer;

Combined

Control type

Local

Climatic modification as per GOST 15150

UHLZ

Ambient operating temperature, °С

+40 … -25

Max. altitude above sea level, m

1,000

Service life, years

30

SITE NAVIGATION

VIDEO ABOUT TCN-ELECTRO PLANT

IMPLEMENTED PROJECTS

GEOGRAPHY OF DELIVERIES

CATALOGUE PRINTED VERSION

©1999-2018 ООО TCN-electro

 

Sale Department for the Nizhny Novgorod region: +7 (831) 275-888-9

Regional sale department (Russia and CIS countries): +7 (495) 789-49-68

 

7 A, ul. Elektrovoznaya, Nizhny Novgorod, Russia, 603108

office@tcn-nn.ru